SCHMIDT Flow Sensor SS 20.420

Производител: Schmidt
Product brochure (11/2024)
Instructions for use (538888.02E)
3D-STP data
EU-Declaration of conformity (01/2024)
UK-Declaration of conformity (01/2024)

Thermal flow sensor for unidirectional or bidirectional measurement of flow velocity of air with simultaneous detection of flow direction.

  • Thermopile head (very fast response time)
  • Flow signal
  • Short probe length of 60 mm and 110 mm
  • Measuring ranges 0 … 1 m/s to 0 … 10 m/s
  • Bidirectional measurement (detection of flow direction, optional)
  • Extremely compact (electronics are integrated into tube)
  • Sensor element protected against mechanical stress
  • Linear analog output for measured flow velocity
  • Plant and mechanical engineering
  • Semiconductor and electronics manufacturing
  • Cleanroom and pharmaceutical
  • Ultra-compact design
  • Sensor tube and sensor head out of stainless steel

Accessories

Connection technology

DescriptionArticle-Number
Power supply unit: output 24 V / 1A DC, supply voltage 115/230 V AC (strip terminal) 535 282

Mounting and fixing technology

DescriptionArticle-Number
Wall mounting flange, stainless steel, clamping ring PTFE 520 181
Wall mounting bracket, aluminium anodized 503 895
Mounting flange, stainless steel 1.4404 551 740
Compresson fitting, stainless steel, G½, atmospheric pressure 532 160
Welding sleeve, stainless steel 1.4571, G½, according to EN 10241, 2 pieces 524 882
Assembly kit for pipe assembly suitable for MD 10.010/10.015 including pipe clamps and collar for adjustment to pipe diameter 531 394

Measured value display

DescriptionArticle-Number
SCHMIDT® LED display MD 10.010; in the wall housing to visualize the volumetric flow and the flow velocity (or other measures), 85…250 V AC and sensor supply 527 320
SCHMIDT® LED display MD 10.010; as with 527 320 but with 24 V DC voltage supply 528 240
SCHMIDT® LED display MD 10.015; in the wall housing to visualize the volumetric flow and the flow velocity (or other measures), with additional sum function and second measuring input, 85 … 250 V AC and sensor supply 527 330
SCHMIDT® LED display MD 10.015; as with 527 330 but with 24 V DC voltage supply 528 250
Technical data
Measuring quantity Standard flow velocity wN, based on standard conditions 1)
Measured medium Clean air or nitrogen
Measuring range wN (±)0 … 1 / 2.5 / 5 / 10 m/s
Lower detection limit wN (±)0.05 m/s
Measuring accuracy
Standard wN ±(5 % of measured value + [1 % of fmr; min. 0.05 m/s]) 2)
High precision (optional) wN ±(3 % of measured value + [1 % of fmr; min. 0.05 m/s]) 2)
Response time (t90) wN 0.2 s
Operating temperature
Sensor 0 … +60 °C
Storage temperature -20 … +85 °C
General data
Humidity Measuring mode: Non-condensing (< 95 % RH)
Operating pressure (max.) Atmospheric (700 … 1,300 hPa)
Supply voltage 12 … 26.4 V DC
Current consumption Typ. < 6 mA (max. 10 mA)
Analog output 0 … 10 V (RL ≥ 10 kΩ; CL ≤ 1 nF; short-circuit protected)
Electrical connection Non-detachable cable, 3 wires, length 5 m, with ferrules
Maximum cable length 15 m
Mounting position ±3° relative to flow direction
Protection type III (SELV or PELV)
Protection class IP65
Probe length 60/110 mm (order option)
Weight Approx. 40 g (sensor llength of 110 mm)
Material
Sensor head Ø 9 mm x 10 mm stainless steel 1.4404
Sensor tube Ø 9 mm stainless steel 1.4404
Cable sheath PVC